Significant acoustic activities that to a high degree of certainty can be traced to partial discharges was discovered in mainly four areas on the high voltage side of the transformer. The high apparent energy and frequency acoustic signals indicate high levels of partial discharge within the transformer. Several areas in the transformer were identified as potential sources of the partial discharges; those areas should be inspected closer.
This resulted in recommendations to monitor the evolution of the partial discharges. Follow-up acoustic measurements to determine the development of partial discharges over time and/or to follow up the effectiveness of any service performed was advised.